H130--Amendment to the Electrical Power Distribution System - Protest
ID: 36C25925Q0292Type: Combined Synopsis/Solicitation
Overview

Buyer

VETERANS AFFAIRS, DEPARTMENT OFVETERANS AFFAIRS, DEPARTMENT OFNETWORK CONTRACT OFFICE 19 (36C259)Greenwood Village, CO, 80111, USA

NAICS

Electrical Contractors and Other Wiring Installation Contractors (238210)

PSC

QUALITY CONTROL- MECHANICAL POWER TRANSMISSION EQUIPMENT (H130)

Set Aside

Service-Disabled Veteran-Owned Small Business (SDVOSB) Set-Aside (FAR 19.14) (SDVOSBC)
Timeline
  1. 1
    Posted Mar 24, 2025, 12:00 AM UTC
  2. 2
    Updated Apr 14, 2025, 12:00 AM UTC
  3. 3
    Due May 10, 2025, 11:00 PM UTC
Description

The Department of Veterans Affairs is seeking proposals for the Electrical Power Distribution System Testing Services at the Western Colorado Health Care System in Grand Junction, Colorado. This procurement, set aside for Service-Disabled Veteran-Owned Small Businesses (SDVOSBC), aims to ensure the reliability and safety of electrical systems through comprehensive testing, inspection, and maintenance of equipment across 16 buildings. The contract, valued at approximately $19 million, includes a range of deliverables such as site surveys, status reports, and a final facility condition assessment, with performance expected to commence in May 2025 and continue through April 2030. Interested contractors should direct inquiries to Contract Specialist Crystal Volmar at crystal.volmar@va.gov or by phone at 303-712-5825, with proposals due by April 18, 2025, at 10:00 AM Mountain Time.

Point(s) of Contact
Crystal VolmarContract Specialist
(303) 712-5825
crystal.volmar@va.gov
Files
Title
Posted
Apr 14, 2025, 9:04 PM UTC
The Arc Flash Hazard Analyses Project at the Veterans Affairs Medical Center in Grand Junction, Colorado, conducted between January and May 2022, aims to assess and enhance safety measures related to electrical arc flash hazards. The document is organized into several critical sections, including an introduction, an executive summary, and detailed analyses including short circuit studies and protective device coordination. The central focus is on the Arc Flash Study, which evaluates the potential risks posed by arc flash events within the facility's electrical system. This structured analysis is essential for understanding and mitigating safety risks, ensuring compliance with safety standards, and protecting personnel from electrical hazards. The findings are presented building by building, offering insights tailored to specific areas within the Medical Center. Overall, this project highlights the commitment of the Veterans Affairs department to uphold safety standards and improve operational reliability within its facilities.
Apr 14, 2025, 9:04 PM UTC
The report details a power quality study conducted at the Veterans Affairs Medical Center in Grand Junction, Colorado, to ensure the electrical system's reliability and safety. The project scope includes creating a one-line diagram of the existing electrical system, assessing the adequacy of equipment ratings against fault currents, reviewing Overcurrent Protective Device settings for optimal coordination, and conducting an arc flash analysis with corresponding equipment labels. Data collection involved onsite discovery, manufacturer ratings, and utility data sourced from the VA’s Engineering Department. Using Easy Power Version 10.5 software, the study performed various power system analyses to evaluate short circuit currents, device coordination, and arc flash exposure levels. The report underscores the importance of these evaluations in maintaining operational integrity and safety within the medical facility's critical environment, with recommendations for addressing maintenance and code compliance issues. Overall, this study is vital for the continued safe operation of essential services at the medical center, reflecting the government's commitment to maintaining high standards in veteran healthcare facilities.
Apr 14, 2025, 9:04 PM UTC
The report outlines findings and recommendations for improving the safety and reliability of electrical systems at the Veterans Affairs Medical Center. It identifies two National Electric Code (NEC) violations regarding overcurrent protection at specific distribution panels. Recommendations include adding appropriately sized protective devices for conductors with reduced ampacity. A short circuit analysis shows that some electrical equipment exceeds its rating, posing safety risks, and suggests replacing inadequate equipment. The report also notes coordination issues among overcurrent protective devices, which complicate fault responses. Additionally, an arc flash study underscores dangerous conditions that cannot be mitigated by personal protective equipment, leading to equipment labeling for safety awareness. The document emphasizes the need for accurate system record maintenance and data completeness for operational review and highlights ongoing safety concerns as crucial for compliance and reliability in electrical systems management.
Apr 14, 2025, 9:04 PM UTC
The Electrical Testing & Maintenance Project at the Veterans Affairs Medical Center in Grand Junction, Colorado, was performed by SDV Services Inc. between January and May 2022 under Contract No. 36C25922P006. The project included a comprehensive evaluation of electrical systems including medium and low voltage equipment, evaluation of grounding systems, thermographic inspections, and voltage assessments. The report identifies areas of concern related to aging electrical components, such as switchboards and transformers, recommending upgrades and replacements for safety and reliability. Key findings emphasize the condition of electrical equipment, particularly those over 15 years and in poor condition, necessitating proactive measures to mitigate risks. Outdoor electrical panels were noted to be vulnerable to environmental damage, prompting recommendations for shelter or improved protective housing. Several issues were highlighted regarding internal connections, working clearances, and the presence of combustible materials that require corrective action per National Electric Code guidelines. The report concludes with suggestions for maintenance practices and the importance of updating technical drawings to ensure compliance and safety for maintenance personnel. Overall, the project's goal was to enhance the safety, reliability, and longevity of the electrical systems at the medical center, ensuring compliant operations that meet current industry standards.
Apr 14, 2025, 9:04 PM UTC
The Arc Flash Hazard Analyses Project for the Veterans Affairs Medical Center in Grand Junction, Colorado, was conducted in partnership with Slocum & Associates, covering data validation from January to May 2022. The primary focus was on ensuring complete and accurate electrical system information to facilitate proper modeling for arc flash incident energy calculations, prioritizing personnel safety. Key processes included the review of outdated electrical drawings from 2009, field verifications to ensure accuracy, and the documentation of various electrical components such as medium voltage substations, transformers, generators, and panelboards. A thermographic inspection was also conducted to identify thermal anomalies within the electrical systems. The extensive report provides detailed equipment data records categorized by building locations, encompassing the specification of cables, breakers, and switchboards, which are critical for assessing electrical safety and code compliance. This project underlines the government's commitment to maintaining infrastructure safety standards in healthcare facilities, ensuring that staff and patients are protected from electrical hazards as part of ongoing RFPs and funding initiatives aimed at facility upgrades and safety regulations.
Apr 14, 2025, 9:04 PM UTC
The document outlines the electrical distribution and infrastructure specifications for the Grand Junction VA Medical Center, covering various components including substations, transformers, switchboards, and panel configurations. It details equipment specifications such as voltage ratings, current capacities, and installation guidelines, alongside notes on wiring and cable layouts to ensure compliance with safety standards. Furthermore, the drawings include references to specific voltage levels, loading parameters, and installation requirements for emergency and normal power systems.
Apr 14, 2025, 9:04 PM UTC
The document outlines a Request for Proposal (RFP) for Electrical Power Distribution System Testing Services at the Grand Junction Veterans Affairs Medical Center (VAMC) in Grand Junction, Colorado. The solicitation number is 36C25925Q0292, and responses are due by April 11, 2025, at 5:00 PM Mountain Time. This procurement is set aside for Service-Disabled Veteran-Owned Small Businesses (SDVOSBC), with the relevant Product Service Code classified as H130 and NAICS code 238210, which pertains to electrical contracting. The contracting office is the Department of Veterans Affairs, specifically the Network Contracting Office NCO 19, located in Greenwood Village, Colorado. The services will be performed at the Western Colorado Health Care System's location at 2121 North Avenue, Grand Junction. Further details and specifications can be found in the attached document referenced in the notice. This solicitation reflects the government’s commitment to engaging veteran-owned businesses in fulfilling its contracting needs.
Apr 14, 2025, 9:04 PM UTC
The document presents an amendment related to the solicitation for a contract by the Department of Veterans Affairs, specifically from the Network Contracting Office NCO 19. The amendment communicates an extension for the submission of offers to April 18, 2025, at 10:00 AM MDT, to accommodate questions raised by potential bidders. Attached materials respond to inquiries about technical specifications, including diagrams and lists of devices at various building sites. Key submissions include details on service scheduling, coordination for semi-annual and triennial inspections, and an inventory of electrical power distribution system components requiring maintenance. The document underscores the importance of detailed responses to ensure all contractors understand the project scope and requirements, thereby promoting compliance and effective bidding practices. Overall, it emphasizes clear communication and adjustments to timelines to facilitate a smoother procurement process within federal guidelines.
Apr 14, 2025, 9:04 PM UTC
The document serves as an amendment to a prior combined solicitation concerning the testing of the electrical power distribution system at the Grand Junction Veterans Affairs Medical Center (VAMC) in Colorado. The solicitation number is 36C25925Q0292, with responses required by April 18, 2025, at 10:00 AM Mountain Time. The contracting office is located in Greenwood Village, Colorado, and the project is set aside for Service-Disabled Veteran-Owned Small Business Concerns (SDVOSBC). Key components of the solicitation include various attachments outlining the project's scope, such as short circuit studies, equipment duty reports, arc flash studies, and pertinent interpretations. It mandates a comprehensive performance analysis of the electrical systems at the facility and reinforces the need for adherence to safety standards as stipulated in the supporting documents. The amendment indicates an emphasis on ensuring the reliability and safety of electrical services crucial to the healthcare operations at the facility. The primary contact for further inquiries is Contract Specialist Crystal Volmar, reachable via email and phone. This document underscores the federal government's commitment to enhancing infrastructure for veteran healthcare.
Apr 14, 2025, 9:04 PM UTC
This document serves as an amendment to a previous combined solicitation, specifically regarding the Electrical Power Distribution System for the Department of Veterans Affairs (VA). The solicitation number is 36C25925Q0292, with responses due by May 10, 2025, at 5:00 PM Mountain Time. The contracting office is located in Greenwood Village, Colorado, and the place of performance is at the Western Colorado Health Care System in Grand Junction, CO. The solicitation is set aside for Service-Disabled Veteran-Owned Small Businesses (SDVOSBC) and falls under the Product Service Code H130, with a corresponding NAICS Code of 238210. The document indicates that Recovery Act funds are not involved and that all amendments and additional information can be found in the attached document referenced as 36C25925Q0292 0002. The primary point of contact for inquiries is Crystal Volmar, a Contract Specialist at the VA. The amendment is crucial for facilitating an organized procurement process and ensuring adherence to relevant regulations and standards for electrical power distribution services within VA facilities.
Apr 14, 2025, 9:04 PM UTC
The document is an amendment regarding a solicitation by the Department of Veterans Affairs (VA), indicating that an agency protest has been received. Consequently, the solicitation is currently on hold pending resolution of the protest. Details provided include the contract ID, requisition/purchase request number, effective date, and the offices administering and issuing the amendment. Contractors are instructed to acknowledge the receipt of this amendment and are informed that a subsequent amendment will be issued with further pertinent details once the protest is resolved. The primary purpose of this document is to formally notify bidders about the status of the solicitation and the necessary actions they must take in response to the changes.
Apr 14, 2025, 9:04 PM UTC
The "Short Circuit Analysis Study" provides an in-depth evaluation of electrical systems, focusing on identifying fault currents that exceed equipment ratings. It comprises three primary sections: Findings and Recommendations, Short Circuit Data, and Short Circuit Calculations. The study highlights safety risks, particularly around panelboards where fault currents may exceed their withstand ratings, and outlines potential solutions, like replacing inadequately rated breakers. The Short Circuit Data section details the modeling and configuration of the electrical system, including essential components such as transformers, cables, and protective devices. It emphasizes the importance of accurate data collection, including physical properties and electrical characteristics for input into analysis software. In the Short Circuit Calculations section, simulations of various fault conditions help assess the adequacy of equipment under possible fault scenarios, ensuring compliance with ANSI/IEEE standards. The study serves as a foundational component for coordinating protections and assessing arc flash risks, ultimately aiming to enhance the safety and reliability of electrical systems. This analysis is essential for government entities and organizations involved in electrical infrastructure to ensure compliance and safe operations across facilities.
Apr 14, 2025, 9:04 PM UTC
The Low Voltage Momentary Report provides essential insights for understanding electrical fault data in power systems, specifically regarding low voltage scenarios. Created with Easy Power Software by ESA, Inc., it includes vital sections that detail the faulted bus location, associated voltages, and fault types, such as 3-phase bolted faults, alongside calculations for Thevenin equivalent fault currents (in kA and MVA). The report outlines the significant contributions of adjacent buses, indicated by fault current and the respective devices involved, facilitating a comprehensive view of network integrity during faults. Additionally, the document presents definitions of technical terms, helping users interpret the data contextually. This report plays a crucial role in assessing fault analysis for electrical systems, ensuring safety and reliability in compliance with regulatory standards, relevant in government RFPs and grants related to energy management and electrical infrastructure projects.
Apr 14, 2025, 9:04 PM UTC
The Equipment Duty Schedule document provides essential guidelines for understanding the evaluation of electrical equipment in relation to fault currents. It details various sections, including header information about the software used, the equipment analyzed, and the fault type, along with pertinent ratings and duties. The table headers cover bus information (name and voltage), equipment specifications (ID, manufacturer, style), and ratings (momentary and interrupting fault current in kilo amps). The 'DUTIES' section analyzes the equipment's momentary and interrupting ratings, comparing these with exposure to available fault currents, which is quantified in percentages. The document emphasizes critical warnings for equipment that either exceeds or approaches its rated limits, indicating safety risks. Overall, the Equipment Duty Schedule serves as a crucial tool for ensuring compliance with operational safety standards in federal and state projects. By identifying potential violations and warnings, it aids in assessing equipment readiness and longevity while assisting in future RFP evaluations by providing standardized criteria for fault current tolerance among equipment, essential for strategic planning and budgeting in government and local grants and RFPs.
Apr 14, 2025, 9:04 PM UTC
The document presents findings from Equipment Duty Reports regarding compliance of various equipment within multiple buildings. The main focus is on the number of equipment categorized by violations and warnings. Overall, one area (Medium Voltage Distribution System, E-1) reported zero violations or warnings, while several buildings showed concerning numbers. E-2 (Bldg 1 North) recorded 18 violations and 13 warnings, and E-3 (Bldg 1 South, 20) had 18 violations with 4 warnings. Additional areas included E-4 (Bldg 1, 39, 45) with 6 violations, E-5 (Bldg 5, 6, 8, 12, 13, 33, 35, 36, 37) with 10 violations, and E-6 (Bldg 9) reporting 8 violations and 1 warning. The document is likely part of a broader governmental effort to ensure compliance with safety standards and regulations across state and local facilities, reflecting the need for ongoing monitoring and potential corrective actions in maintaining operational safety. This assurance highlights the commitment to effective management of equipment standards in government facilities.
Apr 14, 2025, 9:04 PM UTC
The Protective Device Coordination Study aims to optimize the settings and selection of protective devices in electrical power systems to effectively isolate faults while minimizing equipment damage. This process balances conflicting objectives such as quick fault isolation and system sensitivity, known as coordination. The study highlights the importance of selective coordination, particularly for essential electrical systems, to ensure that faults don't affect broader system areas. It outlines that certain systems, primarily those with molded case breakers, currently do not achieve this selective coordination, necessitating further engineering study for compliance and cost assessment. Recommendations rely on time-current curves (TCC) to visualize the relationship between protective devices and their operational characteristics, guiding settings based on ANSI/IEEE and NEC standards. Additionally, the study emphasizes the importance of routine maintenance and calibration of protective devices to maintain system reliability. The findings are categorized into generic information and specific system results, providing a structured approach to enhancing electrical system performance. Overall, this study serves as a crucial guide for improving safety and efficiency in electrical systems, aligning with standards set by electrical codes and engineering practices.
Apr 14, 2025, 9:04 PM UTC
The Coordination Study Reports detail switchgear protective device settings and configurations to ensure effective monitoring and protection in electrical systems. Each report section identifies critical elements such as solid state trip unit (SST) styles, manufacturers, types, sensor ratings, and protective device settings like Long Time Pick Up (LTPU), Long Time Delay (LT Delay), Short Time Pick Up (STPU), and Instantaneous trip settings. The document specifies the settings and functionalities of various trip units, including ground trip and thermal magnetic breakers, detailing their operational thresholds in amps and applicable delay bands. This structure allows for establishing time-current curves essential for electrical coordination studies in compliance with safety regulations. The overarching goal is to ensure safety and efficiency in electrical systems. By documenting these settings and configurations, the report aids stakeholders in understanding the performance characteristics of protective devices, making it instrumental for federal and local RFPs, grants, and regulatory compliance.
Apr 14, 2025, 9:04 PM UTC
The document outlines findings related to Time-Current Curves (TCC) for various electrical systems across multiple buildings, indicating critical issues in protective devices. Key observations reveal that medium voltage (MV) and low voltage (LV) fuses in several locations fail to achieve selective coordination, posing risks of simultaneous failure during faults and inadequate thermal protection for transformers. Specific problems include the ground relay of main breakers that could cut power to entire systems instead of isolating faults to individual feeders, exacerbating potential downtime and operational risk. Recommendations vary from increasing fuse sizes to ensuring feeder breakers are equipped with ground fault relays for improved safety. Overall, the document highlights essential shortcomings in electrical protection systems across different buildings, emphasizing a need for upgrades to ensure effective coordination and protection against faults, thereby aligning with safety standards required for government facilities.
Apr 14, 2025, 9:04 PM UTC
The Arc Flash Study focuses on assessing risks associated with electrical faults and the protective measures personnel should adopt when working on energized equipment. It employs advanced software to evaluate arcing currents and protective device clearing times, ultimately calculating the potential energy released during incidents. The study utilizes IEEE 1584 and NFPA 70E standards for arc flash hazard calculations, contrasting worst-case scenarios based on different arcing time scenarios to provide conservative energy estimates. Key observations include identifying equipment based on incoming cable risks leading to hazardous classifications, emphasizing the necessity of routine maintenance for protective devices to ensure safety compliance, and highlighting the importance of tailored analyses for different situations. The study advocates for periodic testing and maintenance of circuit breakers to prevent operational failures that extend fault clearing times and increase incident energy levels. Ultimately, the report underscores a comprehensive approach to arc flash hazard assessment, combining safety measures with adherence to specified standards for worker protection and equipment safety.
Apr 14, 2025, 9:04 PM UTC
The document provides an in-depth overview of Arc Flash hazards, detailing its causes, effects, and safety standards for electrical systems operating at 120 volts or higher. Arc Flash, resulting from arcing faults that release significant energy in the form of plasma, poses serious risks, including burns and shrapnel injuries. Key regulatory standards to mitigate these risks include OSHA regulations and NFPA safety guidelines. Compliance mandates a comprehensive safety program, personal protective equipment (PPE) requirements, and hazard training for workers. The document emphasizes the importance of thorough Arc Flash Risk Assessments, using the Incident Energy Analysis Method to determine PPE needs based on incident energy exposure. It highlights the critical role of short-circuit and coordination studies in accurately assessing arc fault conditions, warning against overly conservative analysis that may miscalculate the required PPE. Concluding, the document stresses that professional engineering assistance is vital for accurate calculations, helping to minimize PPE requirements and enhancing worker safety while reducing compliance risks and operational inefficiencies. This information is particularly relevant for federal and state compliance RFPs focusing on electrical safety and hazard mitigation in public facilities and infrastructure projects.
Apr 14, 2025, 9:04 PM UTC
The Arc Flash Hazard Reports provide essential information regarding electrical system safety, specifically related to arc flash hazards. Key aspects include identification of faulted buses, equipment types, trip times, and incident energy levels associated with various protective devices. The reports outline technical details such as the bolted fault current, calculated trip times, and opening times of breakers, which are vital for assessing potential electrical hazards. The document serves as a guide to understanding these critical parameters, including the estimated arc flash boundary, working distances, and recommendations for personal protective equipment (PPE) based on incident energy values. Comments within the report further clarify circumstances, including warnings against working on energized equipment when hazards exceed acceptable limits. This report is particularly relevant for government entities and contractors involved in federal and state projects, ensuring compliance with safety standards and regulations while addressing electrical safety in public and private sectors. Proper interpretation of this data is crucial in preventing electrical accidents and ensuring worker safety.
Apr 14, 2025, 9:04 PM UTC
The document serves as a comprehensive glossary of electrical engineering terminology specifically related to power systems. It includes definitions for various components such as 1/C, circuit breakers, and transformers, as well as concepts like derating, short circuits, and selective coordination. Key terms cover equipment specifications, technical standards (e.g., ANSI and IEEE), and safety measures typically involved in electrical operations. The glossary aids in understanding the intricate language of electrical systems, providing clarity on critical aspects such as efficiency ratings, fault conditions, and the relationship between current and voltage. This foundational knowledge is essential for those engaging in federal RFPs, grants, and state/local projects concerning electrical infrastructure, ensuring compliance with industry standards and fostering a common understanding among stakeholders.
Apr 14, 2025, 9:04 PM UTC
This report outlines a power system study conducted using established industry standards, employing Easy Power software for electrical analysis. It focuses on short circuit calculations, protective device coordination, and arc flash evaluations. The findings are contingent upon the integrity of existing configurations and equipment, as any modifications or lack of maintenance may render the results invalid. The report is intended for use by qualified personnel familiar with the specific facility and its engineering principles, emphasizing the importance of reviewing the report for accurate representation of the system. It also states that the preparer disclaims responsibility for inaccuracies from data provided by third parties. Overall, the document serves as a guideline for evaluating electrical systems, critical for federal, state, and local RFPs, ensuring compliance with safety and operational standards.
Apr 14, 2025, 9:04 PM UTC
The document outlines the Building/Study Division Index related to various electrical systems and equipment reports for multiple buildings. It categorizes information by tabs, indicating the specific reports and drawings associated with each building. Key components include momentary reports for medium and low voltage systems, equipment duty reports, time current curves (TCCs), and arc flash hazard assessments. Each tab corresponds to different buildings, detailing their respective electrical characteristics and safety analyses. The final section references oneline drawings, consolidating visuals necessary for understanding the electrical setups. This index serves as a comprehensive resource for tracking electrical system integrity and safety compliance, essential for forthcoming government RFPs and project planning within federal and local grant frameworks.
Apr 14, 2025, 9:04 PM UTC
The document outlines a Request for Proposal (RFP) from the Department of Veterans Affairs (VA) for comprehensive electrical power distribution system testing, inspection, preventative maintenance, and certification services at the Western Colorado Health Care System in Grand Junction, Colorado. The contractor will be responsible for maintaining 16 buildings and ensuring system reliability through regular inspections and compliance with specific standards. Key tasks include semi-annual, annual, and tri-annual service schedules, conducting studies on electrical safety, potential hazards, and making repairs as necessary. The contract, valued at $19 million, includes various deliverables such as site surveys, status reports, calibration certifications, and a final comprehensive facility condition assessment. The timeline for performance spans from May 2025 to April 2030, with specific provisions for working hours to minimize disruption to hospital operations. Contractors must meet strict qualifications, including having registered professionals and certified technicians with experience in electrical testing and maintenance. The proposal emphasizes the VA’s commitment to maintaining high safety standards in healthcare facilities while ensuring operational continuity through rigorous inspection and maintenance of electrical systems.
Lifecycle
Title
Type
Combined Synopsis/Solicitation
Similar Opportunities
J039--Elevator Maintenance and Inspection Testing Services for the Grand Junction CO VA Medical Center
Buyer not available
The Department of Veterans Affairs (VA) is seeking qualified small businesses to provide Elevator Maintenance and Inspection Testing Services for the VA Grand Junction Medical Center in Colorado. The procurement involves a firm-fixed price contract that includes scheduled preventive maintenance, unscheduled repairs, and compliance with safety standards, with a total award amount of $12.5 million over one base year and four option years. This opportunity is crucial for ensuring the operational reliability and safety of elevator systems that serve the veteran community. Interested vendors must submit their proposals by May 16, 2025, following a mandatory site visit on May 7, 2025, and can direct inquiries to Contract Specialist John Cheng at John.Cheng2@va.gov or 303-712-5776.
H161--Electrical Distribution Testing
Buyer not available
The Department of Veterans Affairs is soliciting bids for Electrical Distribution Testing Services at the St. Cloud VA Health Care System, under solicitation number 36C26325Q0682. This procurement is a total small business set-aside, requiring qualified contractors to perform maintenance, inspection, testing, and calibration of the electrical power distribution system from September 1 to December 31, 2025. The services are critical for ensuring the operational safety and efficiency of the VA's healthcare facilities, involving various electrical components such as transformers and circuit breakers, with an emphasis on thorough documentation and reporting. Interested vendors must submit their proposals electronically by April 29, 2025, and direct any inquiries to Contract Specialist Steve Ashby at steve.ashby@va.gov or by phone at 319-887-4935 x63-4935.
Z1DA--PN: 636-25-307, Emergency Electrical System Upgrades (OM)
Buyer not available
The Department of Veterans Affairs is soliciting proposals for the Emergency Electrical System Upgrades project at the Omaha Veterans Affairs Medical Center, designated under Project Number 636-25-307. This project aims to address electrical deficiencies by replacing and installing critical electrical components, with a focus on enhancing emergency power coverage for essential areas such as the inpatient kitchen and elevators. The contract, set aside for Service-Disabled Veteran-Owned Small Businesses (SDVOSB), has a value between $500,000 and $1,000,000, and requires compliance with various safety and operational standards, including a performance period of 365 days. Interested contractors must submit their proposals by April 22, 2025, and can direct inquiries to Contract Specialist Tommy Opal at Tommy.Opal@va.gov or secondary contact Angelique D Mabley at Angelique.Mabley@va.gov.
BB Correct Electrical Deficiencies Lake City, FL PROJECT # 573A4-21-710
Buyer not available
The Department of Veterans Affairs is soliciting proposals for the "Correct Electrical Deficiencies" project at the Lake City VA Medical Center in Florida, identified as Project 573A4-21-710. The objective is to address and rectify electrical deficiencies by providing all necessary labor, materials, and supervision for the renovation, which includes site preparation, demolition, and installation of new electrical systems to enhance safety and compliance with VA standards. This project is particularly significant as it aims to modernize the electrical infrastructure critical for the ongoing operations of the medical facility, ensuring minimal disruption to services provided to veterans. Interested Service-Disabled Veteran-Owned Small Businesses (SDVOSBs) must submit proposals by May 19, 2025, with a project performance period of 730 days from the Notice to Proceed, and can direct inquiries to Amber C. Milton at amber.milton@va.gov or 727-251-2899.
J061--Troubleshoot/Replace MRI Power Conditioner
Buyer not available
The Department of Veterans Affairs is seeking qualified contractors to troubleshoot and replace a faulty MRI power conditioner at the Sheridan Veterans Affairs Medical Center in Wyoming. The procurement involves the replacement of a control power supply board in a Toshiba G8000 UPS Power Conditioner, which is critical for powering a mobile MRI unit used in veteran healthcare services. This contract, identified by solicitation number 36C25925Q0301, has a total award amount of $34 million and is set aside for small businesses, including service-disabled veteran-owned businesses, with responses due by April 30, 2025, at 10 AM Mountain Time. Interested parties should contact Contract Specialist David M. Glanton at David.Glanton@va.gov or 303-717-7075 for further details and to ensure compliance with federal regulations.
Triennial Electrical Testing and Maintenance
Buyer not available
The Department of Veterans Affairs is seeking qualified contractors for the Triennial Electrical Testing and Maintenance contract at the Robert J. Dole VA Medical Center in Wichita, Kansas. This procurement involves comprehensive electrical testing and maintenance services for various equipment and systems, which must be conducted under the supervision of a Registered Professional Engineer and by certified technicians with significant experience. The importance of this contract lies in ensuring the reliability and safety of electrical components, adhering to strict industry standards such as NFPA and ANSI. Interested small businesses should note that the bidding process is set for May 2, 2025, and can contact Hubert W. Scipio at hubert.scipio@va.gov or 913-946-1957 for further details.
Z1MG--SOLAR PV SYSTEM PMIR - Base 4 OY [605] | POP: (05/01/2025 - 09/30/2025)
Buyer not available
The Department of Veterans Affairs (VA) is seeking qualified Service-Disabled Veteran Owned Small Businesses and other small businesses to provide solar photovoltaic (PV) maintenance services at the VA Loma Linda Healthcare System. The objective of this procurement is to ensure comprehensive maintenance, including system management, performance monitoring via a Data Acquisition System (DAS), preventative maintenance, and technical training, for a solar PV system with a total capacity of 1.421 MW-DC. This opportunity is crucial for maintaining the operational efficiency of existing solar arrays and ensuring compliance with safety and performance standards. Interested vendors must submit their qualifications and capability statements by the specified deadlines, with the anticipated period of performance extending from June 1, 2025, through September 30, 2029. For further inquiries, potential bidders can contact Contracting Officer Norman Napper-Rogers at Norman.Napper-Rogers@va.gov or by phone at 602-795-4170.
N061--631-18-003 Correct Deficiency Generator Buildings 1WA, 1EA
Buyer not available
The Department of Veterans Affairs is seeking contractors for the "Correct Deficiencies Generator Buildings 1WA 1EA" project at the VA Central Western Massachusetts Health Care System in Leeds, MA. The project aims to address critical deficiencies in the generator systems, requiring comprehensive site preparation, demolition, and upgrades to electrical and fire suppression infrastructure, with an estimated cost between $1,000,000 and $5,000,000. This initiative is vital for enhancing the operational efficiency and safety of facilities that serve veterans. A Request for Proposal (RFP) will be issued on or about March 29, 2025, with proposals due by May 14, 2025; interested contractors must register in the System for Award Management (SAM) and can contact Contract Specialist Brian Kelly at Brian.Kelly@va.gov or 413-584-4040 x6722 for further information.
Amended DLS Material Handler Contract (VA-25-00000414) for warehouses DLS and SDC
Buyer not available
The Department of Veterans Affairs is seeking proposals for the Amended DLS Material Handler Contract (VA-25-00000414), which involves providing facility support staffing services for material handling at warehouses DLS and SDC in Golden, Colorado. The contract, set aside for Service-Disabled Veteran-Owned Small Businesses (SDVOSB), requires contractors to manage logistics activities such as receiving, storage, inventory control, and distribution of commodities, ensuring compliance with specified performance standards without direct government supervision. Interested parties must submit their proposals by May 9, 2025, at 10:00 A.M. Mountain Time, and can direct inquiries to Bradley Geghan at bradley.geghan@va.gov.
UNINTERRUPTIBLE POWER SUPPLY SYSTEM MAINTENANCE
Buyer not available
The Department of Veterans Affairs is soliciting proposals for the maintenance of Uninterruptible Power Supply (UPS) systems at the Oscar G. Johnson VA Medical Center in Iron Mountain, Michigan. This procurement is exclusively set aside for Service-Disabled Veteran-Owned Small Businesses (SDVOSBs) and encompasses a total project value of $12.5 million over a five-year term, which includes a base year and four optional years. The maintenance services will involve semi-annual preventive services and battery replacements, ensuring compliance with industry standards to maintain operational uptime for critical power systems essential for healthcare facilities. Interested contractors should contact Susan Pasholk at SUSAN.PASHOLK@VA.GOV or call 414-844-4846 for further details, and a site visit is recommended for those considering submission of a proposal.